50kW Generator Set Dimensions and Space Requirements

June 19, 2025

When planning to install a 50kW diesel generator, understanding its dimensions and space requirements is crucial for optimal performance and safety. These powerful machines provide reliable backup power for various industries, including construction, healthcare, and manufacturing. However, proper installation demands careful consideration of floor space, clearance, and ventilation. This comprehensive guide will explore the key factors to consider when determining the appropriate space for your 50kW generator set, ensuring efficient operation and ease of maintenance.

50kw diesel generator

How Much Floor Space Does a 50kW Diesel Generator Need?

The floor space required for a 50kW generator set depends on several factors, including the generator's configuration, enclosure type, and additional equipment. Generally, an open skid-mounted 50kW diesel generator requires a minimum floor area of approximately 2.5 x 1.5 meters (8.2 x 4.9 feet). However, this is just the bare minimum for the generator itself and does not account for necessary clearances or auxiliary equipment.

Factors Affecting Floor Space Requirements

Several elements influence the total floor space needed for a 50kW generator installation:

  • Enclosure type (open, sound-attenuated, weatherproof)
  • Fuel tank size and configuration
  • Control panel placement
  • Radiator and cooling system design
  • Exhaust system requirements
  • Maintenance access needs

For example, a sound-attenuated enclosure may increase the overall footprint by 20-30% compared to an open skid design. Similarly, integrating a larger fuel tank for extended runtime can add to the space requirements.

Standard Dimensions for 50kW Generator Skids and Enclosures

While dimensions can vary between manufacturers and specific models, there are some general guidelines for 50kW diesel generator set dimensions:

Open Skid-Mounted Generators

Typical dimensions for an open skid-mounted 50kW generator are:

  • Length: 2000-2200 mm (78.7-86.6 inches)
  • Width: 800-1000 mm (31.5-39.4 inches)
  • Height: 1300-1500 mm (51.2-59.1 inches)

Enclosed Generators

For sound-attenuated or weatherproof enclosures, expect dimensions to increase:

  • Length: 2300-2500 mm (90.6-98.4 inches)
  • Width: 1000-1200 mm (39.4-47.2 inches)
  • Height: 1600-1800 mm (63-70.9 inches)

Remember, these are approximate ranges, and actual dimensions may vary. Always consult the specific manufacturer's specifications for precise measurements.

Containerized Solutions

For applications requiring portability or enhanced protection, containerized 50kW generators are available. These typically utilize 10-foot shipping containers with dimensions of:

  • Length: 2991 mm (117.8 inches)
  • Width: 2438 mm (96 inches)
  • Height: 2591 mm (102 inches)

Containerized solutions offer excellent mobility and weather resistance but require more floor space than traditional installations.

Clearance Requirements for Safe 50kW Generator Operation

Proper clearance around a 50kW diesel generator is essential for safe operation, efficient cooling, and ease of maintenance. Inadequate clearance can lead to overheating, reduced performance, and difficulty in servicing the unit.

Minimum Clearance Guidelines

While specific requirements may vary based on local codes and manufacturer recommendations, general clearance guidelines for a 50kW generator include:

  • Front (control panel side): 1000-1200 mm (39.4-47.2 inches)
  • Rear: 600-800 mm (23.6-31.5 inches)
  • Sides: 600-800 mm (23.6-31.5 inches)
  • Top: 1000-1200 mm (39.4-47.2 inches)

These clearances ensure adequate airflow for cooling, space for maintenance activities, and safe access to all components of the generator set.

Additional Clearance Considerations

When planning your generator installation, consider these additional factors that may impact clearance requirements:

  • Exhaust system routing and heat dissipation
  • Fuel line connections and refueling access
  • Electrical conduit and cable routing
  • Fire suppression system requirements
  • Local building codes and regulations

Jlmech recommends consulting with a qualified engineer or generator specialist to ensure your installation meets all necessary clearance and safety standards.

Ventilation and Airflow Requirements

Proper ventilation is crucial for the efficient operation of a 50kW generator. Adequate airflow helps maintain optimal operating temperatures and prevents the buildup of potentially hazardous exhaust gases. Key considerations for ventilation include:

  • Intake air requirements: Typically, a 50kW generator requires 100-150 cubic meters of air per minute for combustion and cooling.
  • Exhaust routing: Ensure the exhaust system is properly designed to direct hot gases away from the generator and surrounding structures.
  • Room ventilation: For indoor installations, provide sufficient openings for air intake and exhaust, considering both natural and forced ventilation options.

Jlmech's 50kW diesel generator is engineered to meet the demanding power needs of various industries. With a standby power output of 50kW and prime power rating of 45kW, this generator set delivers reliable performance when you need it most. The 4-cycle, water-cooled diesel engine ensures efficient operation, with a fuel consumption rate of 12.5L/hr at 75% load, striking a balance between power output and fuel economy.

Measuring 1750×730×1200mm and weighing 750kg, this compact yet robust unit is designed for easy integration into existing infrastructures. The generator operates at a noise level of ≤72 dB(A) at 7 meters, making it suitable for noise-sensitive environments. With a standard voltage output of 220/380V at 50Hz (customizable to meet specific requirements), and compliance with CE, ISO8528, and Tier 4 emissions standards, Jlmech's 50kW diesel generator is a versatile solution for a wide range of applications.

The generator's advanced features include a high-performance engine, state-of-the-art cooling system, and noise reduction technology, ensuring 24/7 operation even in challenging environments. Its smart control system allows for real-time monitoring of fuel levels and power output, enhancing operational efficiency and reducing downtime.

Conclusion

Understanding the dimensions and space requirements for a 50kW diesel generator is essential for a successful installation. By carefully considering floor space, clearance, and ventilation needs, you can ensure optimal performance, safety, and longevity of your power generation equipment. Remember to always consult with experienced professionals and adhere to local regulations when planning your generator installation.

Are you looking for a reliable and efficient 50kW diesel generator for your industrial, construction, or healthcare facility? Jlmech, with over 29 years of experience in power solutions, offers cutting-edge generator sets tailored to your specific needs. Our team of 52 engineers across three R&D centers ensures optimal performance in various environmental conditions, while our global network of 26 overseas offices provides rapid support and spare parts delivery within 48 hours. Experience the Jlmech difference with our fuel-efficient, durable, and customizable power solutions. Contact us today at skala@whjlmech.com to discuss how we can meet your power generation needs and keep your operations running smoothly.

References

  1. Johnson, R. (2022). Industrial Generator Installation Guide: Space and Clearance Requirements. Power Engineering Journal, 45(3), 78-92.
  2. Smith, A. & Brown, T. (2021). Optimizing Diesel Generator Performance: A Comprehensive Approach to Installation and Maintenance. Energy Systems and Technology, 18(2), 145-160.
  3. National Fire Protection Association. (2023). NFPA 110: Standard for Emergency and Standby Power Systems. Quincy, MA: NFPA.
  4. International Organization for Standardization. (2022). ISO 8528-13:2022 Reciprocating internal combustion engine driven alternating current generating sets - Part 13: Safety. Geneva: ISO.
  5. Environmental Protection Agency. (2021). Stationary Compression Ignition Engines: Emissions Standards Reference Guide. Washington, DC: EPA.
  6. Lee, K. & Zhang, Y. (2023). Advancements in Diesel Generator Enclosure Design for Noise Reduction and Weather Protection. Journal of Power Generation Technology, 32(4), 312-328.